Model Rating |
4200W/5200VA at 127/220 (120 or 240 degrees only) |
| 4200W/5200VA at 120/208 (120 or 240 degrees) |
| 4200W/6000VA at 120/240 (180 degrees) |
| 4200W/6000VA at 115/230 (180 degrees only) |
| 3780W/5400VA at 110/220 (180 degrees only) |
| 3360W/4800VA at 100/200 (180 degrees only) |
Dimensions (W x D x H) |
6.9 in. x 24.2 in. x 16.9 in. (176 x 615 x 430) |
Racking Units |
4U |
Weight |
161 lbs. |
Nominal Operating Frequency |
50 or 60 Hz (Factory Default = 60) |
Factory Default VAC |
120/208 VAC at 120 degrees |
L1-L2 Factory Default Input Phase Angle |
120 degrees |
Allowable Input Phase Angle |
120, 180, 240 degrees, Auto-sensing on application of AC (Restrictions for L-N voltages other than 120 VAC) |
User Configurable L1-N, L2-N VAC |
100/110/115/120/127 VAC (May be modified using configuration program) |
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation) |
100% - 90% loading: 90 VAC - 140 VAC
90% - 70% loading: 80 VAC - 140 VAC
70% - 30% loading: 70 VAC - 140 VAC
30% - 0% loading: 60 VAC - 140 VAC |
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation) |
100% - 70% loading: 80 VAC - 140 VAC
70% - 30% loading: 70 VAC - 140 VAC
30% - 0% loading: 60 VAC - 140 VAC |
L1-N, L2-N Max. Allowable VAC |
150 VAC |
Input Frequency w/o Battery Operation |
40 - 70 Hz |
Input Power Connection |
See Distribution Box Options |
Factory Default Output VAC |
120/208 VAC @ 120 degrees |
L1-L2 Factory Default Output Phase Angle |
120 degrees |
Allowable Output Phase Angle |
120, 180, 240 degrees Auto-sensing on initial application of input AC |
Factory Default L1-N, L2-N VAC |
120 VAC nominal |
User Configurable L1-N, L2-N VAC |
100/110/115/120/127 VAC, ±3% |
Output Connections |
See Distribution Box Options |
Frequency |
50 Hz or 60 Hz, Nominal |
Waveform |
Sinewave |
Main Mode Overload |
200% for 8 cycles; 130% for 10 seconds with transfer to bypass |
Disable Bypass operation |
If input voltage exceeds ±15% of the nominal voltage |
Re-enable Bypass operation |
If input voltage returns to within ±10% of nominal output voltage |
Disable Bypass operation |
When the input frequency prevents synchronous operation |
Operating Temp |
+32°F to +104°F (0°C to +40°C) |
Storage Temp |
+5°F to +122°F (-15°C to +50°C) |
Relative Humidity |
0% to 95%, non-condensing |
Operating Elevation |
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating |
Storage Elevation |
50,000 ft. (15,000 m) maximum |
Audible Noise |
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides |
Safety |
UL 1778, c-UL Listed (Suitable for computer room applications) |
RFI/EMI |
FCC Part 15, Subpart B, Class A |
Surge Immunity |
IEEE/ANSI C62.41 Category A & B |
Transportation |
ISTA Procedure 1A |
PD-HDWR Distribution Box Amp Rating |
24 Amps |
PD-HDWR Distribution Box Input Power Connection |
4-Wire Hardwired, 8-10AWG |
PD-HDWR Distribution Box Output Power Connection |
4-Wire Hardwired, 8-10AWG |
PD-HDWR Distribution Box Input Branch Circuit Breaker |
30 Amp, Supplied by User |
Server or mission critical device protection. Online provides a pure signal and completely isolates equipment from the power grid.
An On-Line UPS has longer battery life than Stand-By technology. Size the UPS to the load and then add extra battery modules if extended run time is desired. The unit may also be mounted vertically as a free standing tower. Requires 30 Amp service.
Unit comes with rack ears (securing flanges) but these do not support the weight of the unit. An optional rail kit (see below) is required.