Liebert GXT3 UPS Battery Run Times
 

 

Number of Batteries
Model VA
Run Time, Minutes, for Load, W
200
400
600
800
1000
1200
1400
1600
1800
2000
2500
100% Load
Min.
W
Internal Battery
500VA
30
12
             
8
450
700VA
26
14
6
             
6
630
1000VA
28
15
9
5
             
4
900
1500VA
26
16
10
8
5
         
4
1350
2000VA
20
11
10
8
6
5
4
   
4
1800
3000VA
25
20
14
10
9
8
5
4
4
2700

Number of Batteries
Model VA
Run Time, Minutes, for Load, W
200
400
600
800
1000
1200
1400
1600
1800
2000
2500
100% Load
Min.
W
Internal Battery + 1 External Battery Cabinet
500VA
130
80
             
66
450
700VA
126
75
54
             
50
630
1000VA
128
74
52
41
             
27
900
1500VA
110
72
48
36
28
         
24
1350
2000VA
54
34
34
26
22
17
15
   
15
1800
3000VA
102
80
56
50
44
38
26
22
18
2700

Number of Batteries
Model VA
Run Time, Minutes, for Load, W
200
400
600
800
1000
1200
1400
1600
1800
2000
2500
100% Load
Min.
W
Internal Battery + 2 External Battery Cabinet
500VA
220
130
             
116
450
700VA
264
122
88
             
82
630
1000VA
252
126
84
60
             
58
900
1500VA
208
132
94
74
54
         
48
1350
2000VA
120
82
60
52
44
36
29
   
29
1800
3000VA
124
114
106
92
74
66
62
46
44
2700

Number of Batteries
Model VA
Run Time, Minutes, for Load, W
200
400
600
800
1000
1200
1400
1600
1800
2000
2500
100% Load
Min.
W
Internal Battery + 3 External Battery Cabinets
500VA
336
150
             
128
450
700VA
280
140
120
             
116
630
1000VA
320
148
118
80
             
78
900
1500VA
310
204
138
102
90
         
82
1350
2000VA
180
126
92
72
62
52
45
   
45
1800
3000VA
174
150
122
110
105
104
76
62
62
2700

Number of Batteries
Model VA
Run Time, Minutes, for Load, W
200
400
600
800
1000
1200
1400
1600
1800
2000
2500
100% Load
Min.
W
Internal Battery + 4 External Battery Cabinets
500VA
630
210
             
174
450
700VA
560
300
146
             
140
630
1000VA
600
250
138
116
             
109
900
1500VA
400
256
180
144
110
         
100
1350
2000VA
240
166
130
108
94
84
64
   
64
1800
3000VA
184
172
150
128
120
119
105
92
84
2700