Circuit-Conductor Ampacity Rating Chart

Circuit-conductor ampacity and voltage rating for jacketed cords in general-use cord sets and power-supply cords per UL guidance

Types of Cord Size of Conductors in Cord Number of Cord Conductors Number of Current Carrying Conductors1 Ampacity of Current-Carrying Conductors (amperes) Voltage Rating of Cord
0 - 50 ft.
(0 - 15.2 m)
Over 50 ft.
(Over 15.2 m)
S, SO, SOO, ST, STO, STOO, SE, SEO, or SEOO 18 2, 3 or 4
3 or 4
2
3
10
7
7
5.6
600
600
16 2, 3 or 4
3 or 4
2
3
13
10
10
7
600
600
14 2, 3 or 4
3 or 4
2
3
18
15
13
10
600
600
12 2, 3 or 4
3, 4 or 5
2
3
25
20
18
15
600
600
10 2, 3 or 4
3, 4 or 5
2
3
30
25
25
20
600
600
8 2, 3 or 4
3, 4 or 5
2
3
40
35
30
25
600
600
6 2, 3 or 4
3, 4 or 5
2
3
55
45
40
35
600
600
4 2, 3 or 4
3, 4 or 5
2
3
70
60
55
45
600
600
2 2, 3 or 4
3, 4 or 5
2
3
95
80
70
60
600
600
SJ, SJO, SJOO, SJT, SJTO, SJTOO, SJE, SJEO, or SJEOO 18 2, 3 or 4
3 or 4
2
3
10
7
7
5.6
300
300
16 2, 3 or 4
3 or 4
2
3
13
10
10
7
300
300
14 2, 3 or 4
3 or 4
2
3
18
15
13
10
300
300
12 2, 3 or 4
3, 4 or 5
2
3
25
20
18
15
300
300
10 2, 3 or 4
3, 4 or 5
2
3
30
25
25
20
300
300
SV, SVO, SVOO, SVT, SVTO, SVTOO, SVE, SVEO, or SVEOO 18 2 or 3 2 10 7 300
17 2 or 3 2 12 10 300
16 2 or 3 2 13 10 300
1A conductor that is used to carry an unbalanced current from the other conductors is not considered to be a current carrying conductor.